Fire and burn

Gamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke or CO

Recalled 2016-03-31. Fire and burn hazard. Here is what the CPSC published, and what you are owed.

About 1,000Units
2016-03-31Recall date
None reportedInjuries

The text below is quoted from the CPSC notice word for word.

What was recalled
This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.
The hazard
When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
Injuries
No incidents or injuries have been reported.
The remedy
Consumers should immediately contact the distributor to obtain the free repair, a firmware upgrade.

The details

ProductsGamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)
Made inUnited States
CPSC recall number16134
What a recall entitles you to

A refund, a repair or a replacement. The notice says which. It costs you nothing and there is usually no receipt requirement.

Stop using the product first. Recalls do not expire. An old one still counts.

The full CPSC notice, including photographs, is at cpsc.gov.

Source: CPSC SaferProducts recall feed, retrieved 2026-08-06. Newest recall on file 2026-07-30.

More fire and burn recalls  ·  Recalls in 2016  ·  All product recalls